Note: IPm firmware versions are of the form major.minor.buildnumber. A letter X will be appended in the case of unreleased experimental versions. Other letters may be added in the case of patches or other special versions. As such, releases which are not consecutive are to be expected. Anything in between two releases was an intermediate version on the way to the next release.
Jump to series:
IMPORTANT: Firmware versions 7.0 and later support only the following model:
- ST-IPM-8460
7.0.106
2022-01-07
Fixed Issues:
ID | Subject | Description |
---|---|---|
448 | Redundancy - Common IP switch is really slow sometimes | Common IP switchover using Sixnet redundancy was found to be slow, sometimes happening up to 30 seconds after IPM switchover. |
7.0.104
2021-11-17
Fixed Issues:
ID | Subject | Description |
---|---|---|
442 | Reset System COM Port | The Reset System COM Port operation in the Advanced Operations for ST-IPm-8460 is giving error. The COM port is not reset to sixnet UDR. |
7.0.103
2021-11-01
Fixed Issues:
ID | Subject | Description |
---|---|---|
345 | Special Features File Creation | Toolkit not able to create special features file during IPM configuration load basic. |
7.0.102
2021-03-24
New features:
ID | Subject | Description |
---|---|---|
201 | IPM Redundancy | Added Straton Redundancy in RedLion Workbench. |
Fixed Issues:
ID | Subject | Description |
---|---|---|
321 | RedLion Workbench | Change Red Lion Workbench serial Support from portA to Port B. |
320 | RedLion Workbench | Enabled Red Lion Workbench Modbus RTU slave functionality on all serial ports. |
318 | MODBUS | Added support for MODBUS Query which has the Slave ID or Unit ID or slave address range from 0 to 247. |
316 | MODBUS | Modbus TCP/IP slave communications would not recover when port is closed; until port is open and closed again. |
302 | IPM Performance | Merged changes implemented for fix ID 238. |
249 | MODBUS | When Modbus address 248 or above is used as a slave the RTU sxMBeth_client goes to 100%. |
7.0.101
2020-11-13
New features:
ID | Subject | Description |
---|---|---|
IPM | Initial Wide Release | |
190 | IPM Performance | Upgraded Straton runtime to version 9.3. |
Fixed Issues:
ID | Subject | Description |
---|---|---|
180 | IPM Performance | Serial interface is supported to download Straton application. |
IMPORTANT: Firmware versions 6.0 and later support only the following models:
- ST-IPM-8460
6.0.205
2020-11-13
Fixed Issues:
ID | Subject | Description |
---|---|---|
238 | Toolkit Comm Frozen due to High CPU Load | Updated sxetherpeer application to fix high CPU load due to misconfigured or missing ModBus stations. Fixed logic for io update to reduce CPU utilization |
6.0.204
2019-08-8
Fixed Issues:
ID | Subject | Description |
---|---|---|
157 | Station Status Bit | Updated sxetherpeer application to recover TCP/IP transfers to E2 module after network fault. |
6.0.203
2019-07-30
Fixed Issues:
ID | Subject | Description |
---|---|---|
106 | IPM Performance | Updated firmware to deliver accurate scan time as per configuration. |
38 | User Operations | Fixed User Operations bug related to add and delete user. |
Known issues:
ID | Subject | Description |
---|---|---|
157 | Station Status Bit | Sixnet TCP/IP transfers to E2 modules is slow to recover after a network fault. |
6.0.202
2015-09-04
Known issues:
ID | Subject | Description |
---|---|---|
15066 | PPP | The PPP daemon does not run correctly under all test configurations. |
New features:
ID | Subject | Description |
---|---|---|
14271 | Platform | Initial firmware release for new MPC8313-based IPm units (CPU-D). Model numbers are: ST-IPM-8460. |