Sixnet® EtherTRAK®-2 Revision History

Sixnet® EtherTRAK®-2 Revision History

Firmware: 2.07, WebUI: 1.18

2020-06-19

Fixed Issues:

IDSubjectDescription
228FirmwareCJC sensors stop updating temperature reading for a time.
234FirmwareUsing counter reset bits would sometimes result in the counter register reporting random start values.
166FirmwareModbus function code 15 and 16 will not work with passthru or Modbus Master on RS485 port.

Firmware: 2.03, WebUI: 1.18

2015-06-23

New Features:

IDSubjectDescription
6759FirmwareImproved Default Gateway Port Support.

Fixed Issues:

IDSubjectDescription
10062Web UIInability to set the scan feature via the Web UI in some situations.
14268Web UILimit precision for AI Channel Value to 6 decimal places.
14272Web UIFix inability to create tags for AI counters.
14273Web UIAdd TPO channels on AO page when TPO is enabled.
14906Web UIFix DI and DO tag names and descriptions not being committed.
14930Web UIAdd option to disable scaling on 10RTD module.
14936Web UIRemove unprintable character in counters help.
14937Web UIFix Test I/O not working in IE 11.

Firmware: 1.26, WebUI: 1.17

2014-11-13

Fixed Issues:

IDSubjectDescription
12050FirmwareAdd cold junction compensation sensor failover and status code.

Firmware: 1.24, WebUI: 1.17

2014-01-03

New Features:

IDSubjectDescription
6759FirmwareAdd support for high speed counters to E2-MIX-20884.
10648Web UI, FirmwareAdded analog output range selection of 0 to 5V for E2-MIX-20884.
12050FirmwareAdd cold junction compensation sensor failure detection and error code reporting.

Fixed Issues:

IDSubjectDescription
7711Web UIImprove web UI to account for the fact that high speed counter channels 3 and 4 share a timebase in the MIX-24882 module. The web UI now propagates the configuration change to both channels when one is changed.
7731Web UI / OEMRemove unused features from an OEM customized Web UI.
11917FirmwareReturn an error when told to create multiple files with the same name because doing so leads to configuration corruption.
11939Web UIImprove screw terminal assignments and wiring diagram help pages and tables.
11940, 11955FirmwareAdd length verification and bounds checking to Modbus messages so that a too-long Modbus message no longer causes a communications failure.
12011Web UIClarify wording in analog input integration drop down menus.
12209Web UIRemove display of module hardware revision.

Firmware: 1.20, WebUI: 1.16

2012-10-09

New Features:

IDSubjectDescription
10403Web UI, FirmwareAdded support for new device: "E2-MIX-20884".
10124Web UI, FirmwareAdded new heartbeat configuration settings to the watchdog page.
6812Web UIAllow dashes in station names.

Fixed Issues:

IDSubjectDescription
6820Web UIFixed selection of analog units in Test I/O - Full Access.
6798Web UIFixed issue that caused TPO entries to become enabled when the "Use last 8 discrete channels as outputs" checkbox was checked.

Firmware: 1.15, WebUI: 1.15

2012-08-07

Fixed Issues:

IDSubjectDescription
8627Web UIAdded the screw terminal assignments for the "E2-16ISOTC".
8626Web UIFixed screw terminal list for "E2-16DI24", "E2-16DO24", and "E2-16DIAC".
6391Web UIFor the "E2-16DORLY"; added screw terminal assignments and removed the "Analog input integration" and "Turn OFF outputs on communication loss" options in the "Analog Options" page.

Firmware: 1.15, WebUI: 1.14

2012-01-16

New Features:

IDSubjectDescription
8628Web UIAdded Analog Input range settings 62.5 mV, 125 mV, and 250 mV for ISOTC modules.
8625Web UIAdded help information for the Thermocouple Analog Input Integration and Temperature Reporting Mode options.

Fixed Issues:

IDSubjectDescription
7512Web UIFor ET-2 mix modules with 4 high-speed counters, fixed the configuration setting checkbox for the 4th counter.

Firmware: 1.15, WebUI: 1.13

2011-10-18

Fixed Issues:

IDSubjectDescription
8102FirmwareFixed spurious ring communications dropouts.

Firmware: 1.14, WebUI: 1.13

2011-10-05

Fixed Issues:

IDSubjectDescription
8205Web UISupport 0-20 mA AI configuration in web UI for E2/EB-MIX24882

Firmware: 1.13, WebUI: 1.12

2011-08-31

Fixed Issues:

IDSubjectDescription
7764HelpFixed help file's RS-485 lead time and lag time description to match the actual validated values.

Firmware: 1.13, WebUI: 1.11

2011-08-12

Fixed Issues:

IDSubjectDescription
7146Web UIChanged watchdog timeout validation to not allow out of range timeout values.
7603WebserverAdded "Cache-Control: no-cache" HTTP header to prevent caching.

Firmware: 1.12, WebUI: 1.10

2011-07-22

New Features:

IDSubjectDescription
7240MIX288x modulesAdded support for high speed counter inputs in latest rev of MIX288x series modules
7139, 7249E2-16ISO20MAdded support for identifying E2-16ISO20M
7126OEMAdded a new OEM

Fixed Issues:

IDSubjectDescription
7172TCP/IPFixed bug where module could reboot if flooded with traffic.

1.11

2011-05-27

New Features:

IDSubjectDescription
6856E2-MIX24882Added 0-20 mA Analog Output Range to E2-MIX24882

1.10

2011-05-10

New Features:

SubjectDescription
New ModulesAdded E2/EB-16DORLY, E2/EB-16ISOAI, E2/EB-8ISOAI, E2/EB-16ISOTC, E2/EB-8ISOTC

Fixed Issues:

IDSubjectDescription
6668I/O TransferFixed failures when using more than 16 I/O transfers
6535, 6554Modbus UDPFixed UDP driver creating a Modbus reply header using outdated information.

1.09

2010-08-27

New Features:

SubjectDescription
Web UIAdded compressed web interface support to speed up web UI

Fixed Issues:

IDSubjectDescription
3198TCP/IPFixed issue with out of order TCP/IP packets causing false timeouts.